| Introduction: |  
| Measures & scans 3 phase voltage supply and display the line voltage or Line to Neutral Voltage. It also monitors the Under & Over voltage conditions & compare with the Programmed Preset trip levels. In case, it exceeds the preset limits it de-energizes an output relay. The Scanners can be Manually reset. |    | 
| 
 | 
| Features: |  
· Digital 3 phase voltage readout. · Scan time of 5 sec each · Preset under voltage trip( 75% - 95%) adjustable. · Preset over voltage trip( 105% - 120% ) adjustable. · Energizing time delay( 2- 5 sec) · 1 CO( 2 CO) output relay rated 5A/230V AC. · Manual reset · DIN panel cutout flush mounted enclosure.
  |    | 
 | 
 |    | 
| 
 | 
| Application Areas: |  
| Generator panels AMF controls panels UPS control panels Power distribution panel |    | 
| 
 | 
| Technical Specifications: | 
| 
 | 
| 
 | 
 | 
Specifications |  
| 1 | 
Supply voltage | 
System 3 Phase 380 / 415 / 440 V AC±30%; Auxillary 110 / 240 / 380 / 415 / 440 V AC / 24 V DC +20%, -25% |  
| 2 | 
Output relay contacts | 
1 CO (2 CO) |  
| 3 | 
Trip setting | 
Under Voltage 75% - 95% of monitored supply; Over Voltage 105% - 120% of monitored supply |  
| 4 | 
Trip time delay | 
3.5 secs ± 1.5 secs |  
| 5 | 
Reset | 
Auto / Manual |  
| 6 | 
Display | 
3 digit, with 1 V resolution & 4 - 7 Secs Scan time |  
| 7 | 
Monitoring | 
Phase to Phase |  
| 8 | 
Weight | 
1100 gms. |  
| 9 | 
Dimensions (mm) | 
Overall (L x W x D) 144 x 72 x 205; Mounting (L x W) 138 x 66 |    |